1. Supply Kingspan KS Series factory-assembled insulated wall and roof panel system as specified and as shown on drawings.
of CSA Standard S16.1. Structure shall be designed to accommodate AISC and ACI tolerances for dead and live load movement.
a) Submit full width panel sections of 8” long showing joints, insulation, profiles and finishes for architect’s approval.
The following performance tests are considered the minimum acceptable requirements:
a) ASTM E72 -The design load / deflection criteria and fastening pattern shall be verified from witnessed / audited tests using the “Chamber Method” in accordance with ASTM E72. The deflection criteria shall be L/180 for walls and L/240 for roof assemblies.
The rainscreen principle with pressure equalization chamber is present in all aspects of Kingspan insulated wall panel joint design to control rainwater penetration. The pressure equalization chamber is shielded from outside by an overlap between two impermeable panel facings thus minimizing rainwater passage into the joint driven by gravity and air pressure difference. Intercepted rainwater is drained effectively back to the exterior.
b) ASTM E283 -The air leakage shall not exceed 0.001cfm/sq. ft. of wall area at a pressure differential of 20psf when tested in accordance with ASTM E283.
c) ASTM E331 -There shall be no uncontrolled water penetration through the panel joints at a pressure differential of 20psf when tested in accordance with ASTM E331.
d) AAMA 501-94 -Methods of Test for Exterior Walls.
a) ASTM C518 Panels shall provide nominal thermal resistance of R=7.2 / inch thickness when tested in accordance with this standard.
a) Positive wind pressure and negative wind pressure (suction) are continually bending interior and exterior composite panels. The panel shall withstand at least 2 million alternate cycles of L/180 deflection without any evidence of delamination, foam core cracking or permanent deformation.
a) Panels shall exhibit no delamination, surface blisters, permanent bowing or deformation when subjected to cyclic temperature extremes of -20°F (-29°C) to +180°F (+82°C) temperatures for twenty one (21), eight-hour cycles.
a) Panels shall exhibit no delamination or metal interface corrosion when subjected to +140°F (+60°C) temperature and 100% relative humidity for a total of 1200 hours (50 days).
8. Autoclave Test
a) Panels shall exhibit no delamination or shrinkage/melting of the foam core from the metal skins after being subjected in an autoclave to a pressure of 2psig (13.8kPa) at a temperature of +218°F (+103°C) for a period of 2 1/2 hours.
9. Acoustics Test
a) ASTM E90 Panels meet sound transmission STC-25 when tested in accordance with this standard.
10. Toxicity Test
a) Panels shall meet the minimum standards of acceptance as required for fire gas toxicity established in article 15, part 1120 of the New York State Uniform Fire Prevention Code.
1.07 Panel Fire Tests
1. Kingspan panels meet specific building envelope performance criteria and requirements stipulated by US and Canadian building codes. Panels were tested in conformance to UL, ULC, FM, and ASTM approval standards, testing methods and procedures. Kingspan panels are listed and labeled by:
a) Factory Mutual (FM)
b) Warnock Hersey (WH)
2. Fire Endurance Tests
CAN/ULC-S101 | Stay in Place Fire Test 10 minutes Panels remain in place for 10 minutes and no joint fastener required holding panel together |
CAN/ULC-S101 | Stay in Place Fire Test 15 minutes Panels remain in place for 15 minutes with stitching screws |
CAN/ULC-S126 | Fire Spread under Roof Deck Assemblies Test |
CAN/ULC-S127 | Standard Corner Wall Method of Test for Flammability Characteristics of Non-Melting Building Materials |
CAN/ULC-S134 | Standard Method of Fire Test for Exterior Wall Assemblies |
Uniform Building Code (UBC) UBC 26-3 [UL 1715] | Enclosed Room Fire Test |
Uniform Building Code (UBC) UBC 26-4 | Full Scale Multi-Story Fire Test |
ULC/ORD 376 | Fire Growth Full Scale Room |
CAN/ULC-S102 | Standard Method of Test for Surface Burning Characteristics of Building Materials and Assemblies Flame spread index less than 20. Smoke developed classification less than 350 |
ASTM E84 | Standard Method of Test for Surface Burning Characteristics of Building Materials Flame spread index less than 20. Smoke developed classification less than 350 |
FM Standard 4880 Approval for Class 1 fire classification [UL 1040] | Meet the FM Standard 4880 Approval requirements for Class 1 fire classification to a maximum height of 30 feet without sprinkler protection |
FM Standard 4880 (50’) Approval for Class 1 fire classification [UL 1040] | Meet the FM Standard 4880 Approval requirements for Class 1 fire classification to unlimited height |
FM Standard 4881 Approval for Class 1 Exterior Wall Systems | High Velocity Hurricane Zone with Large Missile Impact |
FM Standard 4471 Approval for Class 1 Panel Roofs | Panel roof meets the criteria for fire, wind, foot traffic, hail damage resistance, and water leakage resistance |
1.08 Warranty
1. Panel manufacturer shall offer one (1) year limited warranty, commencing from date of shipment providing panels manufactured to be free from defects in materials and workmanship under normal use and service, excluding panel skin coating (paint finish) which is covered under a separate warranty.
Part 2 – Products
2.01 Panel Design
a) Kingspan KS42 SHADOWLINE vertical panel style with hidden joint fastener, designed for exterior wall, interior wall and ceiling applications.
KS42 SHADOWLINE panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inch long Hex-head type “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
b) Kingspan KS42 CF FLUTED vertical panel style with hidden joint feature and fastener, designed for exterior wall applications.
KS42 CF FLUTED panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Wafer-head type “AB” Torx-drive “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
c) Kingspan KS45 SHADOWLINE vertical panel style with low profile and double overlap tongue and groove side joint, designed for interior wall and ceiling applications.
KS45 SHADOWLINE panels shall use through fasteners applied from the exterior connecting panel to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
d) Kingspan KS42 CF SHADOWLINE vertical panel style with hidden joint fastener, designed for exterior wall and interior wall applications.
KS42 CF SHADOWLINE panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint, connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Wafer-head type “AB” Torx-drive “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
e) Kingspan KS39 RW HIGH RIB wall & roof panel style with high rib profile and standing nested lap seam at the joint with anti-siphon groove, designed for roof & wall applications.
KS39 RW HIGH RIB panels shall use #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer and saddle clips supplied by panel manufacturer. Fasteners and saddle clips shall be applied from the exterior at the panel joint connecting both metal faces to the supporting steel structure.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
f) Kingspan KS42 MICRO-RIB panel style with hidden joint fastener, designed for exterior wall applications.
KS42 MICRO-RIB panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint, connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
g) Kingspan KS36 FLAT EMBOSSED panel style with hidden joint fastener, designed for exterior wall applications.
KS36 FLAT EMBOSSED panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint, connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
h) Kingspan KS36 OPTIMO panel style with hidden joint fastener, designed for exterior wall applications.
KS36 OPTIMO panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint, connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
i) Kingspan KS36 STUCCOTHERM panel style with hidden joint fastener, designed for exterior wall applications.
KS36 STUCCOTHERM panels shall use fasteners and clips applied from the exterior and concealed in the panel side joint, connecting both metal faces to the supporting steel structure. Fasteners used shall be #14 x ____ inches long Hex-head type “B” self-tapping with steel & neoprene washer and 12Ga. stainless steel clip supplied by panel manufacturer.
Sealant shall be applied on the warm side of the female end at panel joint. Factory applied sealant may be optional.
2.02 Materials
1. Facing and liner sheets shall be steel with Stucco Embossed pattern. Steel shall be:
Exterior and interior profiles
i. “SHADOWLINE” profile shall have a low profile repeating on 3” centers and running the longitudinal direction of the panel. Low profiles shall be not more than 1/16” deep x ¾” wide. The panel faces shall be Stucco Embossed. Panel faces can be optionally non-embossed.
ii. “FLUTED” profile shall have four (4) deep flutes and four (4) low profile repeating on 10 ½” centers and running the longitudinal direction of the panel. Flutes shall be not more than 9/32” deep x 2 ½” wide with alternating low profiles not more than 1/16” deep x ¾” wide. The panel faces shall be Stucco Embossed.
iii. “MICRO-RIB” profile shall have a roll-formed design of 1/16” deep accordion flute striated profile repeating on ¾” centers across the panel width and running the longitudinal direction of the panel. The panel faces shall be Stucco Embossed.
vi. “OPTIMO” profile shall have no ribs or striations. The panel faces shall be Smooth.
vii. “STUCCOTHERM” profile shall have no ribs. The panel face shall be sprayed with Acrylic Stucco Finish.
Property | Results | Test Method | |
---|---|---|---|
a. | Closed cell | 95% | ASTM D2856 |
b. | Density | 2.2 – 2.8pcf (35.3 – 44.9kg/m3) | ASTM D1622 |
c. | Compressive Stress (Parallel to Rise) | 42psi (289.5kPa) | ASTM D1621 |
Compressive Stress (Perpendicular to Rise) | 24psi (165.4kPa) | ||
d. | Shear Stress | 17.5psi (120.6kPa) | ASTM C273 |
e. | Tensile Stress | 40psi (275.7kPa) | ASTM D1623 |
f. | Oven Aging at 200°F (93°C) for 1 day | +1% vol. change | ASTM D2126 |
Oven Aging at 200°F (93°C) for 7 days | +3% vol. change | ||
g. | Low Temperature Aging at -20°F (-29°C) for 1 day | 0% vol. change | ASTM D2126 |
Low Temperature Aging at -20°F (-29°C) for 7 days | 0% vol. change |
2.03 Finishes
• A 1.0mil total coating made up of 0.2mil primer and 0.8mil top coat USDA, H of A approved for food contact areas.
b) Epoxy Primer
• A 0.2mil primer only finish for concealed areas or ready to receive site applied top coat c) Plastisol
• A 4.0mil total coating made up of 0.2mil primer and 3.8mil top coat of vinyl Plastisol, USDA and H of A approved for food contact areas
d) Fluoropolymer
• A 1.0mil total coating made up of 0.2mil primer and 0.8mil 70% Kynar 500 color top coat. USDA approved in “Regal White” color
e) Duranar Plus
• A premium1.6mil total coating made up of 0.8mil primer and 0.8mil 70% Kynar 500 or Hylar 5000 color top coat
2.04 Colors
• The exterior and interior faces of Kingspan KS Series foam panels and flashings shall receive factory applied colors:
a) Standard colors b) Custom colors c) Premium colors
Part 3 – Execution
3.01 Inspection
1. Examine alignment of structural steel to ensure conformance to the tolerance requirements of CSA Standard S16.1 and/or AISC Code section 7.13 prior to panel installation and do not proceed until all observed defects are corrected by the contractor.
3.02 Installation
3.03 Handling and Storage
1. The panels shall be handled and stored in accordance with good construction practice to prevent permanent distortion and mechanical damage.
3.04 Damaged Materials
1. Repair or replace damaged materials to the satisfaction of the Architect and/or owner. The cost of repairing or replacing damaged material will be charged to the responsible party.
3.05 Cleaning and Care
All specifications and designs are subject to change without notice. Contact Kingspan Insulated Panels Ltd. for the current set of specifications
End of Specifications